“B” Occupancy Automatic Sprinkler System

General Definitions:

  • IBC (International Building Code, USA):
    • Section 903.2.1.6 mandates automatic sprinkler systems based on factors such as fire area exceeding 12,000 sq. ft. (1,115 m²), locations above or below exit discharge levels, and the presence of laboratories using hazardous materials.
  • BSL (Building Standard Law, Japan):
    • Article 17 requires automatic sprinkler systems for buildings with a floor area greater than 500 m², buildings exceeding 31 meters in height, and buildings containing laboratories or hazardous storage.

Comparison Table:

CriterionIBC (USA)BSL (Japan)
Sprinkler System RequirementRequired if fire area > 12,000 sq. ft. (1,115 m²), above/below exit discharge levels, or laboratories using hazardous materialsRequired if floor area > 500 m², building height > 31 meters, or laboratory/hazardous storage present
Basis for RequirementSize of fire area, vertical egress concerns, and hazardous material risksOverall floor area, building height, and presence of hazardous materials or laboratories
Scope of ApplicationExplicit thresholds for specific occupancy and use-case scenariosClearly defined broader criteria based on size, height, and use type
Compliance and EnforcementEnforced through local building code inspections referencing IBC 903.2.1.6Enforced nationally via standardized inspections under Article 17
Flexibility and AdaptabilityExplicit, prescriptive guidelinesLimited flexibility, clearly defined mandatory installation guidelines
Testing and CertificationCompliance required according to NFPA standards (typically NFPA 13)Compliance required following Japanese Industrial Standards (JIS) and other applicable national standards

Key Differences:

  • IBC: Emphasizes detailed thresholds based on specific scenarios including fire area and hazardous usage.
  • BSL: Provides broader criteria with a clear emphasis on building size, height, and occupancy type, creating stringent mandatory installation thresholds.

Case Study:

5-Story Office Building

  • Honolulu, USA (IBC):
    • Automatic Sprinkler System: Required if the fire area exceeds 12,000 sq. ft., located above or below exit discharge, or if hazardous laboratory uses are present.
  • Toyosu, Japan (BSL):
    • Automatic Sprinkler System: Required, as the floor area exceeds 500 m² and/or building height exceeds 31 meters.

Sprinkler Head Spacing Requirements – IBC/NFPA 13 vs. BSL (Japan) vs. Global Approach

StandardMax SpacingMax Area per HeadMax Distance from Wall
IBC / NFPA 13 (USA)4.6 m (15.0 ft)21 m² (226 ft²)2.3 m (7.5 ft)
BSL (Japan)3.5–4.0 m (11.5–13.1 ft)~21 m² (~226 ft²)2.0 m (6.6 ft)
Global Approach3.5 m (11.5 ft) – Most Restrictive21 m² (226 ft²)2.0 m (6.6 ft) – Most Restrictive



Global Approach:

  • Unified Sprinkler Installation Standards:
    • Establish international standards that clearly define mandatory installation thresholds balancing fire safety risks and economic considerations.
  • Performance-Based Criteria:
    • Create adaptable global guidelines, integrating specific occupancy risks (IBC) with broader size and height thresholds (BSL).
  • Consistent Global Certification and Testing:
    • Develop internationally recognized certification processes and standardized testing methodologies to ensure uniform global compliance.
  • Continuous International Cooperation:
    • Hold regular international forums for updating and refining sprinkler requirements, aligning international practices, and addressing emerging fire safety challenges.
  • Global Education and Training:
    • Implement worldwide educational initiatives targeting architects, engineers, regulatory officials, and facility managers to foster consistent and effective application of harmonized sprinkler system requirements.




IBC (via NFPA 13) — U.S.

Sprinkler TypeMaximum Spacing Between Heads
Standard Spray (Light Hazard – e.g., office areas)15 ft (4.6 m)
Standard Spray (Ordinary Hazard)12 ft (3.7 m)
Maximum Coverage Area per Head225 ft² (21 m²) for Light Hazard
Distance from WallMax 7.5 ft (2.3 m)

🔹 IBC defers sprinkler design details to NFPA 13 (Standard for the Installation of Sprinkler Systems)
🔹 The actual spacing also depends on ceiling height, obstructions, and hazard classification.

Japan – BSL (Building Standard Law)

項目(Criteria)規定内容(Standard Requirement)
スプリンクラーヘッドの最大間隔
Maximum spacing between sprinkler heads
3.5~4.0 m (approx. 11.5–13.1 ft)
1ヘッド当たりの最大被覆面積
Maximum coverage area per head
約 21 m² (approx. 226 ft²)
壁からの最大距離
Maximum distance from wall to sprinkler head
2.0 m (approx. 6.6 ft)

🔸 設計は「自動火災報知設備およびスプリンクラー設備の技術基準(消防法施行規則)」に準拠する必要があります。
🔸 地方自治体の条例や消防署の運用指導が追加される場合があります。

[F] TABLE 903.2.11.6

Additional Locations Where Sprinkler Systems Are Required

SectionSubject / Location Requiring Suppression System
402.5, 402.6.2Covered and open mall buildings
403.3High-rise buildings
404.3Atriums
405.3Underground structures
407.7Group I-2 occupancies
410.6Stages
411.3Special amusement buildings
412.2.4Airport traffic control towers
412.3.6, 412.3.6.1, 412.5.6Aircraft hangars
415.11.11Group H-5 High-Piled Manufacturing (HPM) exhaust ducts
416.5Flammable finishes
417.4Drying rooms
419.5Live/work units
424.3Children’s play structures
428Buildings containing laboratory suites
507Unlimited area buildings
509.4Incidental use areas
1029.6.2.3Smoke-protected assembly seating
IFCSprinkler system requirements per Section 903.2.11.6 of the International Fire Code

[F] 表 903.2.11.6

スプリンクラー設備が追加で要求される施設・用途一覧

該当セクションスプリンクラー設備が要求される施設・用途
402.5、402.6.2屋根付き・屋外型モール建築物
403.3高層建築物
404.3アトリウム(吹き抜け空間)
405.3地下構造物
407.7I-2 用途区分の建築物
410.6舞台(ステージ)
411.3特殊アミューズメント施設
412.2.4空港の航空交通管制塔
412.3.6、412.3.6.1、412.5.6航空機格納庫
415.11.11H-5(高リスク製造)用途の排気ダクト
416.5可燃性仕上げ材を使用する施設
417.4乾燥室
419.5住居兼作業スペース(Live/work units)
424.3子供用プレイ構造物
428実験室スイートを含む建築物
507床面積無制限建築物
509.4付随的使用区画(incidental uses)
1029.6.2.3煙保護付き集会席(Smoke-protected assembly seating)
IFC国際消防規範(International Fire Code) のセクション903.2.11.6に基づくスプリンクラー要件

[F] TABLE 906.3(1)

Fire Extinguisher Requirements for Class A Fire Hazards

CategoryLight (Low) Hazard OccupancyOrdinary (Moderate) Hazard OccupancyExtra (High) Hazard Occupancy
Minimum-rated extinguisher2-A (c)2-A4-A (a)
Max. floor area per unit of “A”3,000 sq ft1,500 sq ft1,000 sq ft
Max. floor area per extinguisher<sup>b</sup>11,250 sq ft11,250 sq ft11,250 sq ft
Max. travel distance to extinguisher75 feet75 feet75 feet

Notes:

  • SI Conversion: 1 foot = 304.8 mm; 1 square foot = 0.0929 m²; 1 gallon = 3.785 L
  • <sup>a</sup> Two 2½-gallon water-type extinguishers are considered equivalent to one 4-A rated extinguisher.
  • <sup>b</sup> See Annex E.3.3 of NFPA 10 for more guidance on applying the maximum floor area limits.
  • <sup>c</sup> Two water-type extinguishers, each rated 1-A, are considered equivalent to one 2-A extinguisher in Light Hazard Occupancies.

[F] 表 906.3(1)

クラスA火災に対する消火器設置基準

区分軽度(低)リスク<br>Light (Low) Hazard Occupancy通常(中)リスク<br>Ordinary (Moderate) Hazard Occupancy高リスク<br>Extra (High) Hazard Occupancy
最小定格消火器2-A (c)2-A4-A (a)
1Aあたりの最大床面積3,000 平方フィート1,500 平方フィート1,000 平方フィート
消火器1台あたりの最大床面積 (b)11,250 平方フィート11,250 平方フィート11,250 平方フィート
消火器までの最大移動距離75 フィート75 フィート75 フィート

注釈:

  • SI換算:1フィート = 304.8 mm、1平方フィート = 0.0929 m²、1ガロン = 3.785 L
  • <sup>a</sup> 2台の 2½ガロン水型消火器は、1台の 4-A 定格消火器と同等とみなされます。
  • <sup>b</sup> 最大床面積の適用に関する詳細は NFPA 10 の附属書 E.3.3 を参照してください。
  • <sup>c</sup> 1-A定格の水型消火器を2台設置することで、軽度リスク(Light Hazard)用途においては1台の2-A定格消火器と同等とみなされます。

[F] TABLE 906.3(2)

Fire Extinguisher Requirements for Flammable or Combustible Liquids with Depths ≤ 0.25 inch

Type of HazardBasic Minimum Extinguisher RatingMaximum Travel Distance to Extinguishers (feet)
Light (Low)5-B or 10-B30 feet or 50 feet
Ordinary (Moderate)10-B or 20-B30 feet or 50 feet
Extra (High)40-B or 80-B30 feet or 50 feet

Notes:

  • SI Conversions: 1 inch = 25.4 mm; 1 foot = 304.8 mm
  • (a) For requirements specific to water-soluble flammable liquids and alternative extinguisher sizing, refer to Section 5.5 of NFPA 10.

[F] 表 906.3(2)

液深0.25インチ(約6.35mm)以下の可燃性または引火性液体に対する消火器設置要件

危険物の種類基本的な最小消火器等級消火器までの最大移動距離(フィート)
軽度(Light / Low)5-B または 10-B30フィート または 50フィート
通常(Ordinary / Moderate)10-B または 20-B30フィート または 50フィート
高リスク(Extra / High)40-B または 80-B30フィート または 50フィート

注釈:

  • 単位換算:1インチ = 25.4 mm、1フィート = 304.8 mm
  • <sup>a</sup> 水溶性の可燃性液体や、その他の代替的な消火器容量に関する要件は、NFPA 10 のセクション5.5を参照してください。